MADGETECH- is a data recording system used to monitor the on/off status of motors. Motor101A
Key Features:
- State101A State Data Logger
- Current Switch
- IFC200 Interface Cable
Availability: 5-7 Business Days
Free shipping on orders over $50!
- Satisfaction Guaranteed
- No Hassle Refunds
- Secure Payments
描述
The Motor101A Includes:
(1) State101A: State Data Logger
(1) Current Switch
(1) IFC200: Interface Cable
The Motor101A was designed to measure and record the on/off status changes for motors or other equipment drawing up to 200 Amps.
Just clamp the Motor101A to a wire and when the current passing through exceeds 150 mA the output changes, providing a voltage for the Motor101A to measure. This device can hold up to 465,578 readings, but memory will only be used if the status has changed.
The Motor101A is compatible with the latest MadgeTech 4 Software making starting, stopping, and downloading simple and easy. Graphical, tabular, and summary data is provided for analysis and can be viewed as customizable engineering units.
MADGETECH-Motor101A Product User Guide.pdf
MADGETECH-Motor101A Specification Sheet.pdf
Additional information
| Brand | MADGETECH |
|---|---|
| Model | MOTOR101A |
| Memory | 465,578 readings |
| Reading Rate | 4 Hz to 1 every 24 hours |
| Baud Rate | 115,200 |
| LED Indicators | Red & Green |
| Push-Button Start | Yes |
| Battery Life | 10 years typical |
| Material | ABS Plastic |
| Dimensions | Data Logger: 1.4 in x 2.2 in x 0.6 in (36 mm x 56 mm x 16 mm) |
| Operating Environment | -15 °C to +40 °C (+5 °F to +104 °F), 10 %RH to 90 %RH non-condensing |
| Required Interface Package | IFC200 |
| Approvals | CE |
| State | / |
| State Resolution | 1 second (reading rate dependent) |
| Amperage Range | 0.15 to 200 Amps |
| Trip Point | 0.15 A (150 mA) fixed (200 mA AC for 50 Hz operation) |
| Status Output | N.O.1.0 A at 30 VAC/DC |
| Housing | Split Core |








MADGETECH 100 is a miniature, temperature data logger The MicroTemp
MADGETECH It is a high-temperature data logger with an M12 probe connector. HiTemp140-M12
Cooper-Atkins Puncture Probe with Heavy Duty Cord 1014
MADGETECH The DHS is a data logging system for validating dry heat sterilization cycles. Includes standard calibration certificate.
MADGETECH is an intrinsically safe, temperature data logger. The Temp1000IS
Cooper-Atkins Pipe Strap Probe 4011
MADGETECH Interface Cable Package for the HiTemp140 and PR140 Data Loggers.IFC400
Reviews
There are no reviews yet.